Integrated Three Phase Current Sensor 3 CTs One Connector Split Core Transformer For Energy Monitoring System

3×100A Input | 25mA Output | Class 0.5 Accuracy | Integrated Three Phase Design

Compact three-phase split core CT designed for smart energy monitoring, power metering, and electrical retrofit applications.

Electrical Performance Parameters

NO. Item Measuring Terminal Measured Value Test Condition Standard Test Instruments
1 Rated Input Current Through-core 100 A 25∘C Transformer calibrator;Precision current transformer;Current & voltage generator;Resistance box;Digital multimeter;Power frequency withstand voltage tester
2 Rated Output Current Crystal Head 25 mA 25∘C
3 Maximum Input Current Through-core 120 A 25∘C
4 Operating Frequency 50/60 Hz 25∘C
5 Accuracy Class 0.5 25∘C
6 Phase Angle Error ≤30′ 25∘C
7 Burden Resistance Crystal Head ≤20 Ω 25∘C
8 Ratio Error Nonlinearity ≤0.2% 25∘C
9 Phase Angle Error Nonlinearity ≤15′ 25∘C
10 Withstand Voltage P-S 4 kVac 1 mA, 1 min
11 Insulation Resistance P-S ≥500 MΩ Rated voltage 500 Vdc
12 Enameled Wire Thermal Class CLASS F (155∘C)
13 Operating Temperature −40∘C∼75∘C
14 Secondary Output UL2464+UL2547 one-drag-three cable, cable length 1.5 m
15 Open-circuit Protection Open-circuit protection component installed on transformer secondary side, open-circuit voltage ≤10 V

Core Product Features

1. Three Phase CTs Integrated Into One Compact Unit

One CT Assembly For Three Phase Current Measurement

Three current transformers are integrated into a single compact housing, enabling three-phase current measurement through one integrated cable connection. This design reduces wiring complexity, minimizes installation space, and improves system integration efficiency.

Buyer Value:

  • Simplified panel wiring
  • Reduced installation time
  • Space-saving solution for compact electrical cabinets

2. Class 0.5 High Accuracy For Reliable Energy Measurement

Stable And Precise Current Measurement Performance

With Class 0.5 accuracy, the CTF16LA provides reliable current measurement performance for smart energy meters, power monitoring systems, and energy management applications.

Key Performance:

  • Accuracy Class: Class 0.5
  • Ratio Error Non-Linearity: ≤0.2%
  • Phase Angle Non-Linearity: ≤15′

The specification confirms the accuracy class as 0.5, with measured non-linearity performance parameters defined in the product specification.


3. Split Core Design For Fast Retrofit Installation

Install Without Disconnecting Existing Cables

The split core structure allows direct installation on existing power cables without cable removal or system shutdown, making it ideal for:

  • Electrical retrofit projects
  • Smart meter upgrades
  • Energy monitoring system installation
  • Existing distribution cabinet upgrades

The specification indicates the CT can be directly mounted on the primary current line and fixed with cable ties.


4. 3×100A Primary Current Measurement With 25mA Output

Optimized Signal Interface For Smart Monitoring Systems

Designed for:

  • Rated primary current: 100A
  • Maximum input current: 120A
  • Secondary output current: 25mA

Suitable for connection with:

  • Smart energy meters
  • Power monitoring devices
  • EMS systems
  • Data acquisition equipment

The product specification lists rated input current 100A, maximum input current 120A, and output current 25mA.


5. Built-In Secondary Open Circuit Protection

Enhanced Safety For Measurement Applications

Integrated secondary protection limits the open circuit voltage to ≤10V, improving operational safety and protecting connected measurement equipment.


6. Wide Industrial Temperature Range

Reliable Operation From -40℃ To +75℃

Designed for demanding electrical environments with a wide operating temperature range:

Operating Temperature:

  • -40℃ to +75℃

Suitable for:

  • Industrial power distribution
  • Outdoor electrical cabinets
  • Renewable energy systems
  • EV charging infrastructure

7. High Electrical Insulation Performance

Safe Isolation For Electrical Monitoring Systems

The CT provides strong electrical insulation performance:

  • Dielectric strength: 4kVac / 1mA / 1min
  • Insulation resistance: ≥500MΩ

Ensures reliable isolation between primary current circuits and measurement systems.

Why CTF16LA Is Different From Conventional Current Transformers

A Compact Three-Phase CT Solution Designed To Simplify Installation, Improve Panel Utilization, And Streamline Energy Monitoring Integration.

Traditional CT Approach CTF16LA Solution
Separate CTs for each phase Three CTs Integrated Into One Unit
More individual wiring One Integrated Connection Interface
More installation space Compact Three Phase Structure
More complex retrofit work Split Core Installation
Additional secondary protection may be required Built-In Open Circuit Protection
General-purpose current measurement Designed For Smart Metering & Energy Monitoring

 